55,883.75 Euro
0 references
111,767.5 Euro
0 references
50.0 percent
0 references
1 August 2016
0 references
21 December 2018
0 references
11 January 2019
0 references
E.S.TR.A. S.P.A. ENERGIA SERVIZI TERRITORIO AMBIENTE
0 references
L'INTERVENTO PREVEDE INIZIALMENTE LO SMANTELLAMENTO COMPLETO DELLE 62 POMPE DI CALORE E DEI RELATIVI CIRCOLATORI TRADIZIONALI PRESENTI SULLA COPERTURA DELL'EDIFICIO. VERRANNO POI INSTALLATE, SU UNA NUOVA PLATEA NELLA ZONA DEI PARCHEGGI DELL'EDIFICIO, DUE POMPE DI CALORE SILENZIATE AD ALTA EFFICIENZA DA 363 KWF E 404 KWT TERMICI CIASCUNA. TALI MACCHINE VERRANNO COLLEGATE IDRAULICAMENTE IN PARALLELO E TRAMITE UNA TUBAZIONE INTERRATA E UN CIRCOLATORE GEMELLARE AD INVERTER, UNO PER MACCHINA, SARANNO COLLEGATE AD UN ACCUMULO INERZIALE CHE SEPARERA IL CIRCUITO PRIMARIO DALLA DISTRIBUZIONE DELL'IMPIANTO DI CLIMATIZZAZIONE DELL'EDIFICIO. IL SERBATOIO INERZIALE, INSTALLATO ALL'INTERNO DI UN NUOVO LOCALE TECNICO REALIZZATO ALL'INTERNO DI UN MAGAZZINO DELL'EDIFICIO IN PROSSIMITA DELLE DUE POMPE DI CALORE, AVRA LA DUPLICE FUNZIONE DI DISCONNETTORE IDRAULICO E DI VOLANO TERMICO. DALL'ACCUMULO INERZIALE SI SVILUPPERA POI IL NUOVO CIRCUITO DI DISTRIBUZIONE PRINCIPALE CHE, TRAMITE UN NUOVO CIRCOLATORE (Italian)